Browse the published rule packs. Pick a jurisdiction + project type to see exactly what we check.
basement_finish_nj_2021 · IRC 2021 + NJ UCC 5:23 · nj
Translated from v0.4 bootstrap rule set. 9 rules covering egress (R310), ceiling height (R305), garage/dwelling separation (R302.6), egress door width (R311.2), basement wall R-value (IECC R402.1.2), header on load-bearing wall (R602.7).
IECC 2021 R402.1.2 (NJ Climate Zone 4-5)IECC_R402.1.2_basement_wall_r_valuev1.0.0warnIECC 2021 R402.1.2, Table R402.1.2 — Climate Zone 4 basement walls: R-15 continuous or R-13 cavity + R-5 continuous. NJ adopts IECC by reference under UCC 5:23-3.18.
IECC 2021 R402.1.2, Table R402.1.2 — Climate Zone 4 basement walls: R-15 continuous or R-13 cavity + R-5 continuous. NJ adopts IECC by reference under UCC 5:23-3.18.
IECC_R402.1.2_basement_wall_r_value289921801065ef05…wallIECC 2021 R402.1.2 (NJ Climate Zone 4-5) — adopted by N.J.A.C. 5:23-3.18IRC 2021 R302.6IRC_R302.6_garage_dwelling_thicknessv1.0.0warnIRC 2021 R302.6 — Dwelling/garage separation: minimum 1/2" gypsum board on the garage side and along structure separating dwelling from garage. Habitable rooms above garages: 5/8" Type X gypsum.
IRC 2021 R302.6 — Dwelling/garage separation: minimum 1/2" gypsum board on the garage side and along structure separating dwelling from garage. Habitable rooms above garages: 5/8" Type X gypsum.
IRC_R302.6_garage_dwelling_thickness2773564a6b979a88…wallIRC 2021 R302.6 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R302.6IRC_R302.6_garage_house_separationv1.0.0infoIRC 2021 R302.6 — Dwelling/garage separation: at minimum 1/2" gypsum (residence side of wall + ceiling); 5/8" Type X if habitable above garage.
IRC 2021 R302.6 — Dwelling/garage separation: at minimum 1/2" gypsum (residence side of wall + ceiling); 5/8" Type X if habitable above garage.
IRC_R302.6_garage_house_separationa8d65e9d267d764a…wallIRC 2021 R302.6 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R305.1IRC_R305.1_ceiling_height_habitablev1.0.0warnIRC 2021 R305.1 — Habitable rooms, hallways, corridors, bathrooms, toilet rooms, and laundry rooms shall have a ceiling height of not less than 7 feet (2134 mm).
IRC 2021 R305.1 — Habitable rooms, hallways, corridors, bathrooms, toilet rooms, and laundry rooms shall have a ceiling height of not less than 7 feet (2134 mm).
IRC_R305.1_ceiling_height_habitabledb1c42aae88eb4ca…roomIRC 2021 R305.1 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R310.1IRC_R310.1_sleeping_room_egress_openingv1.0.0blockerIRC 2021 R310.1 - Basements, habitable attics and every sleeping room shall have not less than one operable emergency escape and rescue opening.
IRC 2021 R310.1 - Basements, habitable attics and every sleeping room shall have not less than one operable emergency escape and rescue opening.
IRC_R310.1_sleeping_room_egress_openingb072d692be11f844…roomIRC 2021 R310.1 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R310.2.1IRC_R310.2.1_egress_window_dimsv1.0.0warnIRC 2021 R310.2.1 — Minimum opening height 24", minimum opening width 20".
IRC 2021 R310.2.1 — Minimum opening height 24", minimum opening width 20".
IRC_R310.2.1_egress_window_dims2e60a20e4dfec919…openingIRC 2021 R310.2.1 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R310.2.1IRC_R310.2.1_egress_window_areav1.0.0blockerIRC 2021 R310.2.1 — Emergency escape and rescue openings: minimum net clear opening 5.7 sq ft (824 sq in), min height 24", min width 20".
IRC 2021 R310.2.1 — Emergency escape and rescue openings: minimum net clear opening 5.7 sq ft (824 sq in), min height 24", min width 20".
IRC_R310.2.1_egress_window_area8d5ec2392866aa4a…openingIRC 2021 R310.2.1 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R311.2IRC_R311.2_egress_door_existsv1.0.0blockerIRC 2021 R311.2 - Not less than one egress door shall be provided for each dwelling unit, side-hinged, with a clear width of not less than 32 inches.
IRC 2021 R311.2 - Not less than one egress door shall be provided for each dwelling unit, side-hinged, with a clear width of not less than 32 inches.
IRC_R311.2_egress_door_exists29407a2b0244d049…projectIRC 2021 R311.2 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R311.2IRC_R311.2_egress_door_widthv1.0.0warnIRC 2021 R311.2 — Egress door minimum width: side-hinged door with min 32" clear width when open at 90°.
IRC 2021 R311.2 — Egress door minimum width: side-hinged door with min 32" clear width when open at 90°.
IRC_R311.2_egress_door_width8638dd4243d71721…openingIRC 2021 R311.2 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R314.3IRC_R314.3_smoke_alarmsv1.0.0blockerIRC 2021 R314.3 - Smoke alarms shall be installed in each sleeping room, outside each separate sleeping area in the immediate vicinity of the bedrooms, and on each additional storey of the dwelling.
IRC 2021 R314.3 - Smoke alarms shall be installed in each sleeping room, outside each separate sleeping area in the immediate vicinity of the bedrooms, and on each additional storey of the dwelling.
IRC_R314.3_smoke_alarms94550918b07b1dc8…projectIRC 2021 R314.3 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R315.3IRC_R315.3_co_alarmsv1.0.0blockerIRC 2021 R315.3 - Carbon monoxide alarms shall be installed outside each separate sleeping area in the immediate vicinity of the bedrooms.
IRC 2021 R315.3 - Carbon monoxide alarms shall be installed outside each separate sleeping area in the immediate vicinity of the bedrooms.
IRC_R315.3_co_alarmsd192280fd4cd14a4…projectIRC 2021 R315.3 — adopted by N.J.A.C. 5:23-3.21IRC 2021 R602.7IRC_R602.7_load_bearing_opening_headerv1.0.0infoIRC 2021 R602.7 — Headers: openings in load-bearing walls require structural headers. Table R602.7(1) gives min sizing for typical span/load combinations.
IRC 2021 R602.7 — Headers: openings in load-bearing walls require structural headers. Table R602.7(1) gives min sizing for typical span/load combinations.
IRC_R602.7_load_bearing_opening_headerfc9577d1c7566cd0…openingIRC 2021 R602.7 — adopted by N.J.A.C. 5:23-3.21Pack target was 50–100 rules for full 16 Delaware coverage (multi-family, change-of-use, NEC electrical, NFPA 54 gas, JC zoning/parking, IECC energy). Each rule needs: a capability + rubric_version + active_version row, plus an entry in this pack's capability_slugs_json. Predicates are author-served code with a SHA-256 fingerprint so the audit trail proves nothing silently drifted.